Parameter
Units
Minimum
Maximum
Default
kPaG
0 kPaD
500 kPaD
1 kPaD
kPaA
MPaG
0.000 MPaD
0.500 MPaD
0.001 MPaD
MPaA
kg/cm²G
0.00 kg/cm²D
5.10 kg/cm²D
0.01 kg/cm²D
kg/cm²A
1.
High Suction Pressure Warning
This parameter is used to select the suction pressure value above which a
High Suction Pressure Warning
will be annunciated. The warning will only be issued if the compressor is running. The value is measured in
the panel pressure units as selected on the
Panel Settings
screen.
2.
High Suction Pressure Warning Start Delay
This parameter is used to select for what period of time the high suction pressure safety parameters will be
ignored after the compressor is started. The value is measured in seconds.
3.
Low Suction Pressure Booster Shutdown
This parameter is used to select the suction pressure value below which a
Low Suction Pressure Shutdown
will be annunciated. The parameter will only appear if the compressor application is set to
Swing
in the con-
figuration. The shutdown will only be issued if the compressor currently operating as a booster. The value is
measured in the panel pressure units as selected on the
Panel Settings
screen.
4.
Low Suction Pressure High Stage Shutdown
This parameter is used to select the suction pressure value below which a
Low Suction Pressure Shutdown
will be annunciated. The parameter will only appear if the compressor application is set to
Swing
in the con-
figuration. The shutdown will only be issued if the compressor currently operating as a high stage. The value
is measured in the panel pressure units as selected on the
Panel Settings
screen.
5.
Low Suction Pressure Shutdown
This parameter is used to select the suction pressure value below which a
Low Suction Pressure Shutdown
will be annunciated. The shutdown will only be issued if the compressor is running. The value is measured in
the panel pressure units as selected on the
Panel Settings
screen.
6.
Low Suction Pressure Warning Offset
This parameter is used to set an offset value added to the
Low Suction Pressure Shutdown
value. If the suc-
tion pressure falls below this calculated value, a
Low Suction Pressure Warning
will be annunciated. The
warning will only be issued if the compressor is running. The value is measured in the panel pressure units
as selected on the
Panel Settings
screen.
7.
Limitation Suction Pressure Load Inhibit Offset
This parameter is used to set an offset value added to the
Low Suction Pressure Shutdown
parameter. If the
suction pressure falls below this calculated value, the compressor will be prevented from loading. The value
is measured in the panel pressure units as selected on the
Panel Settings
screen.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
138
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016