Parameter
Units
Minimum
Maximum
Default
MPaG
-0.300 MPaD
1.000 MPaD
MPaA
kg/cm²G
-3.1 kg/cm²D
10.20 kg/cm²D
kg/cm²A
Low Oil Differential Pressure Start-
ing Shutdown Timer
Seconds
0 s
900 s
See Description
Low Oil Differential Pressure Run-
ning Shutdown Timer
Seconds
0 s
900 s
See Description
Low Oil Differential Pressure Warn-
ing Offset
barG
0.10 barD
10.00 barD
0.10 barD
barA
PSIG
1.5 PSID
145.0 PSID
1.5 PSID
PSIA
kPaG
10 kPaD
1000 kPaD
10 kPaD
kPaA
MPaG
0.010 MPaD
1.000 MPaD
0.010 MPaD
MPaA
kg/cm²G
0.10 kg/cm²D
10.20 kg/cm²D
0.10 kg/cm²D
kg/cm²A
Low Oil Differential Pressure Warn-
ing Timer
Seconds
0 s
600 s
See Description
Low Oil Differential Run Delay
Seconds
1 s
30 s
See Description
1.
High Oil Differential Pressure Shutdown
This parameter is used to select the maximum allowable differential in oil pressure. If the differential exceeds
this value, a
High Oil Differential Pressure Shutdown
will be annunciated. The maximum allowable value for
this parameter is set in the configuration. The default value of this parameter is dependent on the selected
compressor manufacturer. The value is measured in the panel pressure units as selected on the
Panel Set-
tings
screen.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
128
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016