14.
Suction Bypass Timer
This parameter is used to select the amount of time that the suction bypass solenoid will remain energized
after the compressor has started. The value is measured in seconds.
15.
Fast Unload Running Timer
This parameter is used to select the amount of time for which the compressor will be permitted to run while
the compressor is in fast unload mode. The parameter will only be visible if the
Fast Unload
option is ena-
bled in the configuration. The value is measured in seconds.
16.
External Capacity Mode
This parameter is used to determines if the external capacity exerts direct control over the load/unload sole-
noids or simply communicates the need for increased or decreased capacity to the compressor. The options
are:
•
Direct Pulse Control
•
Indirect Pulse Control
17.
Remote Control Mode Interface
This parameter is used to select the method of communication used between the panel and any remote
capacity control devices. The options are:
•
Network
•
Hard Wired
18.
Suction Check Valve Close Assist Pulse Timer
This parameter is used to select the length of the control pulses used to operate close assist feature of the
motorized suction check valve. The parameter will only be visible if the
Suction Check Valve Close Assist
option in the compressor configuration is set to
Normally Open Pulsed
or
Normally Closed Pulsed
. The value
is measured in seconds.
19.
Control Mode After Shutdown
This parameter is used to select whether the compressor will be permitted to resume operation in remote
mode following a shutdown condition. The options are:
•
Enabled
•
Disabled
20.
Sequencer Control
This parameter is used to select the type of control panel which will sequence this compressor. The options
are:
•
GEA Omni – This option indicates that the compressor will be sequenced by another GEA Omni panel.
•
GEA FES Legacy Panel – This option indicates that the compressor will be sequenced by an older gen-
eration of GEA control panel.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
112
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016