3.1.15
Oil Temperature
Parameter
Units
Minimum
Maximum
Default
High Oil Temperature Shutdown
°C
18.3 °C
200.0 °C
79.4 °C
°F
65.0 °F
392.0 °F
174.9 °F
High Oil Temperature Warning Off-
set
Kelvin
0.0 K
70.0 K
5.6 K
F°
0.0 F°
90.0 F°
10.0 F°
Low Oil Separator Temperature
°C
18.3 °C
200.0 °C
18.3 °C
°F
65.0 °F
392.0 °F
65.0 °F
Low Oil Temperature Warning Off-
set
Kelvin
0.0 K
70.0 K
5.6 K
F°
0.0 F°
90.0 F°
10.0 F°
Low Oil Temperature Start Delay
Seconds
0 s
600 s
300 s
1.
High Oil Temperature Shutdown
This parameter is used to select the oil temperature value above which a
High Oil Temperature Shutdown
will be annunciated. The shutdown will only be issued if the compressor is running. The value is measured in
the panel temperature units as selected on the
Panel Settings
screen.
2.
High Oil Temperature Warning Offset
This parameter is used to set an offset value subtracted from the
High Oil Temperature Shutdown
parame-
ter. If the oil temperature exceeds this calculated value, a
High Oil Temperature Warning
will be annunci-
ated. The warning will only be issued if the compressor is running. The value is measured in the panel tem-
perature units as selected on the
Panel Settings
screen.
3.
Low Oil Temperature Shutdown
This parameter is used to select the value of the oil temperature below which a
Low Oil Temperature Shut-
down
will be annunciated. The shutdown will only be annunciated if the compressor is running. The value is
measured in the panel temperature units as selected on the
Panel Settings
screen.
4.
Low Oil Temperature Warning Offset
This parameter is used to set an offset value added to the
Low Oil Temperature Shutdown
parameter. If the
oil temperature falls below this calculated value, a
Low Oil Temperature Warning
will be annunciated. The
warning will only be issued if the compressor is running. The value is measured in the panel temperature
units as selected on the
Panel Settings
screen.
5.
Low Oil Temperature Start Delay
This parameter is used to select for what period of time the low oil temperature parameters will be ignored
after the compressor is started. This value is measured in seconds.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
134
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016