3.
Outlet Temperature
•
High Outlet Temperature Warning
If the compressor is running and the outlet temperature exceeds this value for a set time, a
High Outlet
Temperature Warning
will be issued.
•
High Outlet Temperature Warning Timer
The period of time before
High Outlet Temperature Warning
will be issued.
•
Low Outlet Temperature Shutdown
If the compressor is running and the outlet temperature exceeds this value for a set time, a
Low Outlet
Temperature Shutdown
will be issued.
•
Low Outlet Temperature Shutdown Timer
The period of time before
Low Outlet Temperature Shutdown
will be issued.
•
Low Outlet Temperature Warning Offset
This value is an offset from
Low Outlet Temperature Shutdown
. If the compressor is starting or running
and the outlet temperature exceeds this value, a
Low Outlet Temperature Warning
will be issued.
•
Low Outlet Temperature Warning Start Delay
The period of time after the compressor has started that
Low outlet Temperature Warning
is ignored.
•
Limitation Outlet Temperature Load Inhibit Offset
This annunciation will be triggered if the compressor outlet temperature falls below the set point calcu-
lated by adding the value of the
Limitation Outlet Temperature Load Inhibit Offset
parameter to the
Low
Outlet Temperature Shutdown
parameter.
•
Limitation Outlet Temperature Force Unload Offset
This value is an offset from
Low Outlet Temperature Shutdown
. If outlet temperature goes below this
value the compressor will be forced to unload.
3.6
Refrigerant Sensor Control Parameters
Control parameters are displayed on OmniData screen detailed in Section 2.4, Page 26. Below is a list of all con-
trol parameters and a brief description of their function. One set of parameters is provided for each individual
sensor.
3.6.1
Refrigerant Sensor
Hint!
The heading of each set of refrigerant parameters will be the name of the associated sensor
as entered in the Configuration screen. For further information, refer to Section 2.4, Page 26
Control
Refrigerant Sensor Control Parameters
Instruction Manual | GEA Omni™