Set Point Selection Digital Input
This check box is used to select if the panel is equipped with a digital input to control the current control
set point remotely.
19.
Motor Current and Capacity Output
This check box is used to select if the panel is equipped with analog outputs to retransmit the compres-
sor motor current and capacity.
20.
Permissive Start
This check box is used to select if the panel is equipped with a digital input which must be energized to
allow the compressor to start.
21.
Hot Gas Bypass
This check box is used to enable control of the Hot Gas Bypass solenoid, which is typically used to keep
the machine running under low load conditions.
22.
Starting Bypass
This check box is used to enable control of a suction to discharge bypass solenoid so as to reduce the
torque required to start the compressor.
23.
Hall Spring Slide Valve Return
This check box is used to select if the compressor is equipped with a spring to force the slide valve back
to zero if the compressor is stopped without unloading. This option is only enabled for Hall compressor
retrofit applications.
24.
Fast Unload
This check box is used to enable control of the fast unload solenoid for retrofit applications.
25.
Double Balance Piston Output
This check box is used to enable control of a double balance piston solenoid. This option is only used for
HE series compressors. This option may not be modified in the field.