Parameter
Units
Minimum
Maximum
Default
Low Suction Superheat
Shutdown Timer
Seconds
0 s
900 s
30 s
Superheat Discharge
Annunciations
Selection – See Description
High Discharge Super-
heat Shutdown
Kelvin
0.0 K
150.0 K
100.0 K
°F
0.0 °F
270.0 °F
180.0 °F
High Discharge Super-
heat Shutdown Timer
Seconds
0 s
900 s
80 s
Low Discharge Superheat
Shutdown
°C
0.0 K
150.0 K
0.0 K
°F
0.0 °F
270.0 °F
0.0 °F
Low Discharge Superheat
Shutdown Timer
Seconds
0 s
900 s
80 s
1.
Superheat Suction Annunciations
This parameter is used to select whether the panel suction superheat calculations are configured to trigger
shutdown annunciations.
2.
High Suction Superheat Shutdown
This parameter is used to select the
Suction Superheat
temperature above which a
High Suction Superheat
Shutdown
will be annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter
has been set to
Enabled
. The shutdown will only be issued if the compressor is starting or running. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
3.
High Suction Superheat Shutdown Timer
This parameter is used to select the period of time that the
Suction Superheat
value must remain above the
value of the
High Suction Superheat
parameter before a
High Suction Superheat Shutdown
is annunciated.
This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The
value is measured in seconds.
4.
Low Suction Superheat Shutdown
This parameter is used to select the
Suction Superheat
temperature below which a
Low Suction Superheat
Shutdown
will be annunciated. This parameter will only be visible if the
Superheat Annunciations
parameter
has been set to
Enabled
. The shutdown will only be issued if the compressor is starting or running. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
5.
Low Suction Superheat Shutdown Timer
This parameter is used to select the period of time that the
Suction Superheat
value must remain below the
value of the
Low Suction Superheat
parameter before a
Low Suction Superheat Shutdown
is annunciated.
This parameter will only be visible if the
Superheat Annunciations
parameter has been set to
Enabled
. The
value is measured in seconds.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
149