4.2.8
List and Description of Refrigerant Sensor Warnings
Warning
Explanation
Refrigerant Sensor High Warn-
ing
This annunciation will be triggered if the parts per million reading on any
refrigerant sensor exceeds the
Refrigerant Sensor High Warning
parameter
for the period of time defined by the
Refrigerant Sensor High Warning Delav’
parameter.
Refrigerant Sensor High High
Warning
This annunciation will be triggered if the parts per million reading on any
refrigerant sensor exceeds the
Refrigerant Sensor High High Warning
parameter for the period of time defined by the
Refrigerant Sensor High High
Warning Delay
parameter.
4.2.9
List and Description of Oil Still Warnings
Warning
Explanation
No Oil Still Return Activated
This annunciation will be triggered if the Oil Return attempts to initiate while
no compressors are running.
4.2.10
List and Description of Other Warnings
Warning
Explanation
Auxiliary Warning
This annunciation will be triggered if the Auxiliary Warning input becomes de-
energized. This warning will only be issued if the Auxiliary Warning option
has been enabled in the configuration.
Math Block Units Mismatch
Warning
This annunciation will be triggered if the inputs of a Math block in the logic
diagram are expressed in different units.
Sensor Failure Warning
This annunciation will be triggered if the reading of a sensor is outside its
defined range. This annunciation will be triggered if the compressor can con-
tinue to run safely without the failed sensor.
Please contact GEA High Log
Usage
This annunciation will be triggered if an unusual amount of information is
being written to the activity log.
Math Block Units Mismatch
This annunciation will be triggered if a Math block in the logic diagram is
receiving two different unit types as input.
Annunciations
Warnings
Instruction Manual | GEA Omni™
Control panel
222
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016