Parameter
Units
Minimum
Maximum
Default
Outlet Temperature
High Outlet Temperature Warning
°C
-75 °C
100 °C
100 °C
High Outlet Temperature Warning
Timer
Seconds
0 s
300 s
120 s
Low Outlet Temperature Shutdown
°C
-60 °C
200 °C
-20 °C
Low Outlet Temperature Shutdown
Timer
Seconds
0 s
300 s
120 s
Low Outlet Temperature Warning
Offset
K
0.0 K
50.0 K
5.0 K
Low Outlet Temperature Warning
Start Delay
Seconds
0 s
300 s
120 s
Limitation Outlet Temperature Load
Inhibit Offset
K
0.1 K
50.0 K
10.0 K
Limitation Outlet Temperature
Force Unload Offset
K
1.0 K
50.0 K
5.0 K
1.
Secondary Refrigerant
•
Secondary Refrigerant Feedback Flow Delay
This parameter is used to select the amount of time the panel will wait to trigger a Secondary Refrigerant
Feedback Flow Warning or Shutdown. The value is measured in seconds.
•
Secondary Refrigerant Pump Stop Delay
This parameter is used to select the period of time the pump will continue to run after the compressor
has stopped. The value is measured in seconds.
•
Secondary Refrigerant Feedback Pump Delay
This parameter is used to select the amount of time the panel will wait to trigger an Secondary Refriger-
ant Pump Feedback Warning. The value is measured in seconds.
Control
Evaporator Control Parameters
Instruction Manual | GEA Omni™
Control panel
172
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016