1.
Oil Return Transfer Mode
This parameter is used to select the method of oil return employed by the oil still. It is only visible on Oil Stills
utilizing York style control. The options are:
•
Manual
•
Automatic
•
Rapid Return
2.
Oil Return Automatic Transfer Day
This parameter is used to select which day of the week an automatic oil return cycle will occur. It is only
visible on Oil Stills utilizing York style control when the
Oil Return Mode
parameter is set to
Automatic
. Any
day of the week may be selected if an automatic oil return cycle is desired once a week, or
Once A Day
may
be selected if a return should occur automatically every day.
3.
Oil Return Automatic Transfer Hour
This parameter is used to select the specific hour, counting up from midnight, in which an automatic oil
return will be initiated on any day that a return is scheduled to occur as selected in the
Oil Return Automatic
Transfer Day
parameter. It is only visible on Oil Stills utilizing York style control when the
Oil Return Mode
parameter is set to
Automatic
. The value is measured in hours.
4.
Oil Return Automatic Transfer Minute
This parameter is used to select the specific minute, within the hour selected in the
Oil Return Automatic
Transfer Hour
parameter in which an automatic oil return will be initiated on any day that a return is sched-
uled to occur as selected in the
Oil Return Automatic Transfer Day
parameter. It is only visible on Oil Stills
utilizing York style control when the
Oil Return Mode
parameter is set to
Automatic
. The value is measured
in Minutes.
5.
Hot Gas Return Cycle Timer
This parameter is used to select the period of time for which a hot gas return cycle will remain active. It is
only visible on Oil Stills utilizing York style control which are configured for Hot Gas Oil Return. The value is
measured in seconds.
6.
Heater On Temperature
This parameter is used to select the temperature value below which the oil still heater will be permitted to
run. It is only visible on Oil Stills utilizing York style control which are configured for an analog temperature
probe. The value is measured in the panel temperature units as selected in the
Panel Settings
screen.
7.
Heater Off Temperature
This parameter is used to select the temperature value above which the oil still heater will not be permitted to
run. It is only visible on Oil Stills utilizing York style control which are configured for an analog temperature
probe. The value is measured in the panel temperature units as selected in the
Panel Settings
screen.
8.
Oil Drain
This parameter is used to select the period of time that the oil still will remain in Oil Drain mode. It is only
visible on Oil Stills utilizing Berlin style control. The value is measured in seconds.
9.
Drain Delay
This parameter is used to select the period of time that the oil still will wait before entering Oil Drain. It is only
visible on Oil Stills utilizing Berlin style control. The value is measured in seconds.
Control
Oil Still Control Parameters
Instruction Manual | GEA Omni™
Control panel
156
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016