4.
Manual Control Vi Setting
This parameter is used to select the desired Vi value during manual operation. This parameter will only be
visible if the
Vi Mode
option in the
Compressor Configuration
is set to
Continuous Variable
and the
Vi Opera-
tion Mode
parameter is set to
Manual
. The value is unit less.
5.
Volume Slide Adjustment Factor
This parameter is used to select the amount that the volume slide must deviate from the point where the
optimum position was last calculated before the calculations will be reevaluated. This parameter will only be
visible if the
Vi Mode
option in the compressor configuration is set to
Continuous Variable
and if the com-
pressor brand is set to
Vilter
. The value is measure in percent.
6.
Low-Medium Vi Transfer Point
This parameter is used to select the point where the current Vi step will switch between Low and Medium.
The parameter will only be visible if the Vi Mode is set to
Step Variable
in the compressor configuration. The
value is measured in Vi.
7.
Low-Medium Vi Transfer Dead Band
This parameter is used to select the range above and below the
Low-Medium Transfer Point
within which no
Vi step changes will occur. If the Vi reading rises above this range while the current step is
Low
the Vi step
will transfer to
Medium
, and if it falls below the range while the current step is
Medium
the Vi step will trans-
fer to
Low
. The value is measured in Vi.
8.
Medium-High Vi Transfer Point
This parameter is used to select the point where the current Vi step will switch between Medium and High.
The parameter will only be visible if the Vi Mode is set to
Step Variable
in the compressor configuration. The
value is measured in Vi.
9.
Medium-High Vi Transfer Dead Band
This parameter is used to select the range above and below the
Medium-High Transfer Point
within which no
Vi step changes will occur. If the Vi reading rises above this range while the current step is
Medium
the Vi
step will transfer to
High
, and if it falls below the range while the current step is
High
the Vi step will transfer
to
Medium
. The value is measured in Vi.
10.
Stepped Manual Vi Control Setting
This parameter is used to manually set the current Vi Setting for the compressor. The parameter will only be
visible if the Vi Mode is set to
Step Variable
in the compressor configuration. The options are:
•
Low
•
Medium
•
High
3.1.4
Motor
Parameter
Units
Minimum
Maximum
Default
Accumulated Runtime Hours
Hours
0.0 h
1.0 x 10
9
h
0.0 h
Motor Start to Start Delay
Minutes
0.0 min
9999.0 min
20.0 min
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
114
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016