Parameter
Units
Minimum
Maximum
Default
Low Outlet Temperature Warning
Start Delay
Seconds
0 s
300 s
120 s
Limitation Outlet Temperature Load
Inhibit
°C
0.1 K
50.0 K
10.0 K
°F
0.2 °F
90.0 °F
18.0 °F
Limitation Outlet Temperature
Force Unload
°C
0.1 K
50.0 K
5.0 K
°F
0.2 °F
90.0 °F
9.0 °F
1.
High Outlet Temperature Warning
This parameter is used to select the value of the outlet oil temperature above which a
High Outlet Tempera-
ture Warning
condition will be annunciated. The parameter will only be visible if the control signal of the com-
pressor is currently set to
Outlet Temperature
. The value is measured in the current temperature units of the
panel as selected on the
Panel Settings
screen.
2.
High Outlet Temperature Warning Timer
This parameter is used to select the period of time that the Outlet Temperature must exceed the value of the
High Outlet Temperature Warning
parameter before the warning will be annunciated. The parameter will only
be visible if the control signal of the compressor is currently set to
Outlet Temperature
. The value is meas-
ured in seconds.
3.
Low Outlet Temperature Shutdown
This parameter is used to select the value of the outlet oil temperature below which a
Low Outlet Tempera-
ture Shutdown
condition will be annunciated. The parameter will only be visible if the control signal of the
compressor is currently set to
Outlet Temperature
. The value is measured in the current temperature units of
the panel as selected on the
Panel Settings
screen.
4.
Low Outlet Temperature Shutdown Timer
This parameter is used to select the period of time that the Outlet Temperature must remain below the value
of the
Low Outlet Temperature Shutdown
parameter before the shutdown will be annunciated. The parame-
ter will only be visible if the control signal of the compressor is currently set to
Outlet Temperature
. The value
is measured in seconds.
5.
Low Outlet Temperature Warning Offset
This parameter is used to set an offset added to the Low Outlet Temperature Shutdown parameter. If the
outlet temperature falls below this calculated value, a
Low Outlet Temperature Warning
will be annunciated.
The warning will only be issued if the compressor is running. The parameter will only be visible if the control
signal of the compressor is currently set to
Outlet Temperature
. The value is measured in the panel tempera-
ture units as selected on the
Panel Settings
screen.
6.
Low Outlet Temperature Warning Start Delay
This parameter is used to select the amount of time the compressor will be permitted to run after starting
before a
Low Outlet Temperature Warning
condition will be annunciated. The parameter will only be visible if
the control signal of the compressor is currently set to
Outlet Temperature
. The value is measured in sec-
onds.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
146
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016