3.
Lamp Test
Holding this button will turn on all lamps connected to the panel. This function is used to ensure that all
lamps and their associated wiring are working properly.
4.
Move Commissioned Files
This button is used during startup once the panel has been installed. When this button is pressed, the
panel will clear out all erroneous data, warning and log reports generated during the installation process.
This button may only be used once, and only a user with
Service
level or higher permissions may access
it.
Hint!
It is mandatory to press the Move Commissioned Files button once installation of the
panel has been completed.
2.12.5
Logic Tab
This tab is only visible if the panel contains custom programming. It displays a real time representation of the
logic diagram used for custom controls.
fig.86:
Logic diagram tab display
The user may switch between pages of the diagram using the tabs at the bottom of the display, navigate through
the selected page by clicking and dragging along the display and zoom in or out using the slider beneath the
page tabs.
The node on the blocks displayed in the diagram are color coded based on the type of signal they transmit or
receive. An analog node is black, a digital node is blue and a node that may transmit or receive either type is
colored orange. The lines between nodes also change to display their current value or state. Connections
between digital nodes will either appear as a solid green line for an energized signal, or a dotted red line for a
Instruction Manual | GEA Omni™
Control panel
User interface
Service
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016