Parameter
Units
Minimum
Maximum
Default
Temperature High Warning Delay
Seconds
0 s
60 s
0 s
Temperature Low Warning Offset
°C
0.00 °C
40.0 °C
2.0 °C
°F
0.0 °F
72.0 °F
3.6 °F
Temperature Low Warning Delay
Seconds
0 s
60 s
0 s
1.
Set Point
This parameter is used to choose the desired value at which the evaporator zone will attempt to maintain the
zone temperature. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
2.
Set Point Delay
This parameter is used to select the period of time that the zone temperature must remain outside the range
defined by the dead band parameter before adjustments will be made in the zone control. The value is
measured in seconds.
3.
Dead Band
This parameter is used to define a range above and below the set point within which no action will be taken
to adjust the zone temperature. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
4.
Temperature High Warning Offset
This parameter is used to define an offset added to the set point. If the temperature exceeds this value, a
warning condition will be annunciated. The value is measured in the panel temperature units as selected on
the
Panel Settings
screen.
5.
Temperature High Warning Delay
This parameter is used to select the period of time for which a high evaporator temperature condition must
persist before a warning condition will be annunciated. The value is measured in seconds.
6.
Temperature Low Warning Offset
This parameter is used to define an offset subtracted from the set point. If the temperature falls below this
value, a warning condition will be annunciated. The value is measured in the panel temperature units as
selected on the
Panel Settings
screen.
7.
Temperature Low Warning Delay
This parameter is used to select the period of time for which a low evaporator temperature condition must
persist before a warning condition will be annunciated. The value is measured in seconds.
Control
Evaporator Control Parameters
Instruction Manual | GEA Omni™
Control panel
166