Liquid Feed
•
Set Point
This parameter is used to choose the desired value at which the panel will attempt to maintain the liquid
level. The value is measured in percent.
•
Proportional Term
This parameter is used to set the proportional gain for PI control of the device. This value is multiplied by
the total error between the actual and desired values. The value is unitless.
•
Integral Term
This parameter is used to set the rate at which the PI controller will change its integral gain based on the
calculated error over time. The value is measured in samples per Repeat (s/R).
•
Dead Band
This parameter is used to define a range above and below the Set Point within which no action will be
taken to adjust the liquid level. The value is measured in percent.
•
Maximum Level
This parameter is used to select the Maximum Level. If the liquid level is higher a delay time will be
started to trigger a warning or shutdown. The value is measured in percent.
•
High Level Warning Delay (Liquid Feed Maximum Level Warning Delay)
This parameter is used to select the period of time for which a Maximum Level condition must persist
before a Max Liquid Level Warning condition will be annunciated. The value is measured in seconds.
•
High Level Shutdown Delay (Liquid Feed Maximum Level Shutdown Delay)
This parameter is used to select the period of time for which a Maximum Level condition must persist
before a Max Liquid Level Shutdown condition will be annunciated. The value is measured in seconds.
Instruction Manual | GEA Omni™
Control panel
Control
Evaporator Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016