4.
Illegal Oil Filter Differential Pressure Warning Timer
This parameter is used to select the period of time that an
Illegal Oil Filter Differential
condition may remain
before an
Illegal Oil Filter Differential Pressure Warning
will be annunciated. The value is measured in sec-
onds.
5.
Oil Filter Pipe Loss Adjustment
This parameter is used to set the anticipated loss in oil pressure between the inlet and outlet of the oil filter.
This value will be added to the
Oil Filter Differential Pressure
value. This parameter will only be visible if the
compressor is equipped with an oil filter outlet pressure transducer but is not equipped with an inlet oil filter
pressure transducer. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
3.1.14
Oil Separator
Parameter
Units
Minimum
Maximum
Default
Oil Separator Temperature Set
point
°C
18.3 °C
200.0 °C
18.3 °C
°F
65.0 °F
392.0 °F
65.0 °F
High Oil Separator Temperature
Shutdown
°C
18.3 °C
200.0 °C
82.2 °C
°F
65.0 °F
392.0 °F
180.0 °F
High Oil Separator Temperature
Warning Offset
Kelvin
0.0 K
70.0 K
8.3 K
F°
0.0 F°
126.0 F°
14.9 F°
Low Oil Separator Temperature
Shutdown
°C
18.3 °C
200.0 °C
18.3 °C
°F
65.0 °F
180.0°F
65.0 °F
Low Oil Separator Temperature
Warning Offset
Kelvin
0.0 K
70.0 K
5.6 K
F°
0.0 F°
126.0 F°
14.9 F°
High Oil Separator Level Shutdown
Timer
Seconds
0 s
600 s
5 s
High Oil Separator Level Warning
Timer
Seconds
0 s
300 s
5 s
Low Oil Separator Level Else Shut-
down Timer
Seconds
1 s
900 s
180 s
Low Oil Separator Level Stop Shut-
down Timer
Seconds
1 s
900 s
30 s
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
132
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016