Parameter
Units
Minimum
Maximum
Default
Condenser Unit Stop Delay
Seconds
0 s
1800 s
0 s
Condenser Flow Switch Warning
Delay
Seconds
0 s
60 s
30 s
1.
Start Condition
This Parameter is used to select the start condition of the condenser.
2.
Feedback Condenser Unit Delay
This Parameter is used to set a delay time. If the compressor is in the state
Starting
or
Running
the time will
be started. If the time is elapsed before the feedback of the condenser unit is set to true a warning will be
annunciated.
3.
Condenser Unit Stop Delay
This Parameter is used to set a delay time. The time will be started after the compressor state has changed
to
Stopped
. After the time is elapsed the release of the condenser unit will be resettled.
4.
Condenser Flow Switch Warning Delay
This Parameter is used to set a delay time. If the compressor is in the state
Starting
or
Running
the time will
be started. If the time is elapsed before the condenser flow switch detects flow a warning will be annunci-
ated.
3.5
Evaporator Control Parameters
Control parameters are displayed on the main Evaporator screen detailed in Section 2.7.2, Page 48. Below is a
list of all control parameters and a brief description of their function.
3.5.1
Cooling
Parameter
Units
Minimum
Maximum
Default
Set Point
°C
-56.7 °C
204.4 °C
-1 °C
°F
-70.1 °F
399.9 °F
30.2 °F
Set Point Delay
Seconds
0 s
300 s
5 s
Dead Band
°C
0.00 °C
100 °C
2.0 °C
°F
0.0 °F
180.0 °F
3.6 °F
Temperature High Warning Offset
°C
0.00 °C
40.0 °C
2.0 °C
°F
0.0 °F
72.0 °F
5.0 °F
Instruction Manual | GEA Omni™
Control panel
Control
Evaporator Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
165