8.
Automatic Start Offset
This parameter is used to select an offset value added to the value of the Set point. If the control signal
exceeds this calculated value, the compressor will attempt to start. The parameter will only be visible if the
Automatic Start Stop
parameter is set to
Offsets
. The maximum value, minimum value and units of the
parameter are dependent on the chosen control signal:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
9.
Automatic Start Delay
This parameter is used to select the period of time that must elapse after the conditions to automatically start
the compressor are met before it will be permitted to start. In most circumstances the control signal must
exceed the value of the
Automatic Start
parameter in order for an automatic start to occur. The exception is
when the control signal is set to
Discharge Pressure
, where the value must instead remain below the
Auto-
matic Start
parameter. This parameter is only visible if the
Automatic Start Stop
parameter is not set to
Disa-
bled
. The value is measured in seconds.
10.
Automatic Stop
This parameter is used to select the control signal value at which the compressor will stop. This parameter is
only visible if the
Automatic Start Stop
parameter is not set to
Disabled
. The maximum value, minimum value
and units of the parameter are dependent on the chosen control signal:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
11.
Automatic Stop Offset
This parameter is used to select an offset value added to the value of the Set point. If the control signal falls
below this calculated value, the compressor will stop. The parameter will only be visible if the
Automatic Start
Stop
parameter is set to
Offsets
. The maximum value, minimum value and units of the parameter are
dependent on the chosen control signal:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
107