Parameter
Units
Minimum
Maximum
Default
kPaG
-101 kPaG
2413 kPaG
827 kPaG
kPaA
0.00 kPaA
2514 kPaA
928 kPaA
MPaG
-0.101 MPaG
2.413 MPaG
0.827 MPaG
MPaA
0.00 MPaA
2.514 MPaA
0.928 MPaA
kg/cm²G
0.00 kg/cm²G
24.61 kg/cm²G
8.43 kg/cm²G
kg/cm²A
0.00 kg/cm²A
25.64 kg/cm²A
9.43 kg/cm²A
Low Discharge Pressure Warning
Delay
Seconds
0 s
30 s
0 s
1.
High Discharge Pressure Warning
This parameter is used to select the condenser discharge pressure value above which a
High Discharge
Pressure Warning
will be annunciated. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
2.
High Discharge Pressure Warning Delay
This parameter is used to select the period of time for which a high condenser discharge pressure condition
must persist before a high warning condition will be annunciated. The value is measured in seconds.
3.
Low Discharge Pressure Warning
This parameter is used to select the condenser discharge pressure value below which a
Low Discharge
Pressure Warning
will be annunciated. The value is measured in the panel pressure units as selected on the
Panel Settings
screen.
4.
Low Discharge Pressure Warning Delay
This parameter is used to select the period of time for which a low condenser discharge pressure condition
must persist before a low warning condition will be annunciated. The value is measured in seconds.
3.3.4
Condenser Control
Parameter
Units
Minimum
Maximum
Default
Schedule Selection
Selection – See Description
Control
Condenser Sequencer Control Parameters
Instruction Manual | GEA Omni™
Control panel
160
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016