4.2.1
List and Description of Compressor Warnings
Warning
Explanation
High Motor Current Warning
This annunciation will be triggered if the motor current reading exceeds the
value obtained by subtracting the
High Motor Current Warning Offset
param-
eter from the
High Motor Current Shutdown
parameter.
High Suction Pressure Warning This annunciation will be triggered if the suction pressure reading exceeds
the value obtained by subtracting the
High Suction Pressure Warning Offset
parameter from the
High Suction Pressure Warning
parameter.
High Discharge Temperature
Warning
This annunciation will be triggered if the discharge temperature reading
exceeds the value obtained by subtracting the
High Discharge Temperature
Warning Offset
parameter from the
High Discharge Temperature Shutdown
parameter.
High Discharge Pressure Warn-
ing
This annunciation will be triggered if the discharge pressure reading exceeds
the value obtained by subtracting the
High Discharge Pressure Warning Off-
set
parameter from the
High Discharge Pressure Shutdown
parameter.
High Oil Separator Tempera-
ture Warning
This annunciation will be triggered if the oil separator temperature reading
exceeds the value obtained by subtracting the
High Oil Separator Tempera-
ture Warning Offset
parameter from the
High Oil Separator Temperature
Shutdown
parameter.
Low Oil Separator Temperature
Warning
This annunciation will be triggered if the oil separator temperature reading
falls below the value obtained by adding the
Low Oil Separator Temperature
Warning Offset
parameter to the
Low Oil Separator Temperature Shutdown
parameter.
High Oil Separator Level Warn-
ing
This annunciation will be triggered if the oil separator high level input
becomes de-energized for a period of time that exceeds the value of the
High Oil Separator Level Warning Timer
.
High Oil Temperature Warning
This annunciation will be triggered if the oil separator temperature reading
exceeds the value obtained by subtracting the
High Oil Separator Tempera-
ture Warning Offset
parameter from the
High Oil Separator Temperature
Shutdown
parameter.
Low Oil Temperature Warning
This annunciation will be triggered if the oil temperature reading falls below
the value obtained by adding the
Low Oil Temperature Warning Offset
parameter to the
Low Oil Temperature Shutdown
parameter.
High Oil Filter Differential Warn-
ing
This annunciation will be triggered if the calculated oil filter differential
exceeds the value obtained by subtracting the
High Oil Filter Differential
Warning Offset
parameter from the
High Oil Filter Differential Shutdown
parameter.
Instruction Manual | GEA Omni™
Control panel
Annunciations
Warnings