Warning
Explanation
Outlet Temperature Force
Unload
This annunciation will be triggered if the compressor outlet temperature rises
above the set point calculated by subtracting the value of the
Limitation Out-
let Temperature Force Unload Offset
parameter from the
Low Outlet Tem-
perature Shutdown
parameter.
Outlet Temperature Load Limit
This annunciation will be triggered if the compressor outlet temperature rises
above the set point calculated by subtracting the value of the
Limitation Out-
let Temperature Load Inhibit Offset
parameter from the
Low Outlet Tempera-
ture Shutdown
parameter.
Discharge Pressure Force
Unload
This annunciation will be triggered if the compressor discharge pressure
rises above the set point calculated by subtracting the value of the
Limitation
Discharge Pressure Force Unload Offset
parameter from the
High Discharge
Pressure Shutdown
parameter.
Discharge Pressure Load Limit
This annunciation will be triggered if the compressor discharge pressure
rises above the set point calculated by subtracting the value of the
Limitation
Discharge Pressure Load Inhibit Offset
parameter from the
High Discharge
Pressure Shutdown
parameter.
Ammonia Storage Pressure
Load Limit
This annunciation will be triggered if the compressor outlet temperature rises
above the set point calculated by subtracting the value of the
Limitation
Ammonia Storage Pressure Load Limit Offset
parameter from the
Low
Ammonia Storage Pressure Shutdown
parameter.
Ammonia Storage Pressure
Force Unload
This annunciation will be triggered if the compressor ammonia storage pres-
sure rises above the set point calculated by subtracting the value of the
Limi-
tation Ammonia Storage Pressure Force Unload Offset
parameter from the
Low Ammonia Storage Pressure Shutdown
parameter.
Instruction Manual | GEA Omni™
Control panel
Annunciations
Warnings
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
219