5.
Schedule table
This table displays all steps that will be executed by the condenser sequencer during normal panel
operation.
fig.37:
Condenser schedule table
a.
Current step
This icon indicates which step is currently being executed by the sequencer.
b.
Previous timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the previous step. This column will not appear if the
Hide
Timers
button has been clicked.
c.
Soak timer
This column contains the period of time that the sequencer must remain on the current step
before determining if it should step ahead to the next step, step back to the previous step, or
remain on the current step. This column will not appear if the
Hide Timers
button has been
clicked.
d.
Next timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the next step. This column will not appear if the
Hide Timers
button has been clicked.
e.
Condenser devices
These columns each correspond to an individual condenser device. The contents of each cell
dictate what action the device will take during the associated step. The options are:
–
Run
This option is only available for single speed fans and pumps. It will cause the device to
activate during the associated step.
–
Stop
This option is available for all devices. It will cause the device to deactivate during the asso-
ciated step.
–
Hold
Instruction Manual | GEA Omni™
Control panel
User interface
Condenser
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016