4.
Pump Down
This parameter is used to select the period of time that the zone will remain in the pump down stage during
defrost. The value is measured in minutes.
5.
Hot Gas
This parameter is used to select the period of time that the zone will remain in the hot gas stage during
defrost. The value is measured in minutes.
6.
Bleed
This parameter is used to select the period of time that the zone will remain in the bleed stage during defrost.
The value is measured in minutes.
7.
Fan Delay
This parameter is used to select the perios of time that the zone will remain in the fan delay stage during
defrost. The value is measured in minutes.
8.
Post Defrost Temperature Warning Delay
This parameter is used to select the period of time for which temperature warning annunciations will be disa-
bled following a defrost cycle. The value is measured in minutes.
9.
Defrost Group Number
This parameter is used to group evaporator zones based on their proximity to one another. Zones that share
an area will have the same group number. Only one evaporator zone per group may be in defrost mode at
any given time.
10.
Daily Defrost 1
This parameter is used to select the a specific time when the zone will be instructed to enter a defrost cycle.
This feature may be disabled by setting the parameter to
Disabled
.
11.
Daily Defrost 2
This parameter is used to select the a specific time when the zone will be instructed to enter a defrost cycle.
This feature may be disabled by setting the parameter to
Disabled
.
12.
Daily Defrost 3
This parameter is used to select the a specific time when the zone will be instructed to enter a defrost cycle.
This feature may be disabled by setting the parameter to
Disabled
.
13.
Daily Defrost 4
This parameter is used to select the a specific time when the zone will be instructed to enter a defrost cycle.
This feature may be disabled by setting the parameter to
Disabled
.
14.
Daily Defrost 5
This parameter is used to select the a specific time when the zone will be instructed to enter a defrost cycle.
This feature may be disabled by setting the parameter to
Disabled
.
15.
Defrost Termination By Temperature
This parameter is used to select whether the zone will end a defrost cycle once the evaporator coil tempera-
ture exceeds value of the
Defrost Termination Temperature
Parameter.
Hint!
This parameter requires the use of a surface mount temperature sensor which is placed on the
coldest section of the evaporator coil associated with the zone.
Instruction Manual | GEA Omni™
Control panel
Control
Evaporator Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
169