Parameter
Units
Minimum
Maximum
Default
Refrigerant Sensor High Warning
Enabled
Selection – See Description
Refrigerant Sensor High Warning
ppm
0 ppm
100000 ppm
20.0 ppm
Refrigerant Sensor High Warning
Delay
Seconds
0 s
999 s
5 s
Refrigerant Sensor High High
Warning Enabled
Selection – See Description
Refrigerant Sensor High High
Warning
ppm
See Description
Refrigerant Sensor High High
Warning Delay
Seconds
0 s
999 s
5 s
Refrigerant Sensor High High Shut-
down Enabled
Selection – See Description
Refrigerant Sensor High High Shut-
down
ppm
0 ppm
100000 ppm
20.0 ppm
Refrigerant Sensor High High Shut-
down Delay
Seconds
0 s
999 s
5 s
1.
Refrigerant Sensor High Warning Enabled
This parameter is used to select whether the sensor is configured to annunciate a high refrigerant warning
condition. The options are:
•
Enabled
•
Disabled
2.
Refrigerant Sensor High Warning
This parameter is used to select the refrigerant level above which a high warning condition will be triggered.
It will only appear if the
Refrigerant Sensor High Warning
parameter is set to
Enabled
. The value is meas-
ured in parts per million.
3.
Refrigerant Sensor High Warning Delay
This parameter is used to select the period of time for which a high refrigerant warning condition must persist
before an annunciation will be triggered. It will only appear if the
Refrigerant Sensor High Warning
parameter
is set to
Enabled
. The value is measured in seconds.
Instruction Manual | GEA Omni™
Control panel
Control
Refrigerant Sensor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
175