Parameter
Units
Minimum
Maximum
Default
Liquid Solenoid Valve Runtime
Minutes
0 min
32000 min
0 min
Pump Down
Minutes
0.0 min
480.0 min
20.0 min
Hot Gas
Minutes
0.0 min
480.0 min
20.0 min
Bleed
Minutes
0.0 min
480.0 min
20.0 min
Fan Delay
Minutes
0.0 min
480.0 min
20.0 min
Post Defrost Temperature Warning
Delay
Minutes
0.0 min
480.0 min
20.0 min
Defrost Group Number
Unitless
0
80
1
Daily Defrost 1
Selection – See Description
Daily Defrost 2
Selection – See Description
Daily Defrost 3
Selection – See Description
Daily Defrost 4
Selection – See Description
Daily Defrost 5
Selection – See Description
Defrost Termination By Tempera-
ture
Selection – See Description
Defrost Termination Temperature
°C
0.00 °C
325 °C
75.0 °C
°F
32.0 °F
617 °F
167.0 °F
1.
Liquid Solenoid Runtime Defrost
This parameter is used to enable the Liquid Solenoid Valve Runtime Defrost control. The options are
Ena-
bled
and
Disabled
.
2.
Liquid Solenoid Valve Runtime Until Defrost
This parameter is used to select the period of time that the liquid solenoid valve will remain open before ini-
tiating a defrost cycle. This parameter will only be visible if the
Liquid Solenoid Runtime Defrost
parameter is
set to
Enabled
. The value is measured in minutes.
3.
Liquid Solenoid Valve Runtime
This parameter is used to display the amount of time that the zone’s liquid valve has run since the previous
defrost. The value is measured in minutes.
Control
Evaporator Control Parameters
Instruction Manual | GEA Omni™
Control panel
168
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016