3.1.11
Oil Pump Interlock
Parameter
Units
Minimum
Maximum
Default
Illegal Oil Pump Interlock Shutdown
Timer
Seconds
1 s
60 s
5 s
Oil Pump Loss of Lead Interlock
Warning
Seconds
1 s
60 s
5 s
Oil Pump Loss of Interlock Shut-
down Timer
Seconds
1 s
60 s
5 s
1.
Illegal Oil Pump Interlock Shutdown Timer
This parameter is used to select the amount of time the panel will wait to trigger an
Illegal Oil Pump Interlock
Shutdown
if the oil pump interlock signal is received while the oil pump is not running. The value is meas-
ured in seconds.
2.
Oil Pump Loss of Lead Interlock Warning
This parameter is used to select the period of time that the system will wait before annunciating a
Loss of
Interlock Warning
for the lead oil pump. The parameter will only be visible if the compressor is configured
with dual oil pumps. The value is measured in seconds.
3.
Oil Pump Loss Of Interlock Shutdown Timer
This parameter is used to select the amount of time the panel will wait to trigger a
Loss of Interlock Shut-
down
if the oil pump interlock signal is lost while the oil pump is running. The value is measured in seconds.
3.1.12
Oil Differential Pressure
Parameter
Units
Minimum
Maximum
Default
High Oil Differential Pressure Shut-
down
barG
1.00 barD
See Description
See Description
barA
PSIG
14.5 PSID
PSIA
kPaG
100 kPaD
kPaA
MPaG
0.500 MPaD
MPaA
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
126
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016