16.
Defrost Termination Temperature
This parameter is used to select the temperature value of the evaporator coil above which a defrost cycle will
automatically end. It will only be visible if the
Defrost Termination By Temperature
Parameter is set to
Ena-
bled
. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
3.5.4
Suction Valve Settings
Parameter
Units
Minimum
Maximum
Default
Suction Valve Open During Satis-
fied Stages
Selection – See Description
1.
Suction Valve Open During Satisfied Stages
This parameter is used to select whether the zone suction valve will remain open while the zone is satisfied.
The options are:
•
Enabled
•
Disabled
3.5.5
Invert Solenoid Output
Parameter
Units
Minimum
Maximum
Default
Liquid
Selection – See Description
Suction
Selection – See Description
Hot Gas
Selection – See Description
Soft Hot Gas
Selection – See Description
Bleed
Selection – See Description
Fans
Selection – See Description
1.
Liquid
This parameter is used to select whether the Liquid solenoid output is inverted. The options are
Disabled
,
where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
2.
Suction
This parameter is used to select whether the Suction solenoid output is inverted. The options are
Disabled
,
where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
3.
Hot Gas
This parameter is used to select whether the Hot Gas solenoid output is inverted. The options are
Disabled
,
where the solenoid functions normally, and
Enabled
, where the solenoid output is inverted.
Control
Evaporator Control Parameters
Instruction Manual | GEA Omni™
Control panel
170
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016