1.
Oil Separator Temperature Set Point
This parameter is used to select the temperature value that should be maintained in the separator while the
compressor is not running. This parameter will only be visible if the compressor is configured for oil separa-
tor heater control. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
2.
High Oil Separator Temperature Shutdown
This parameter is used to select the temperature value in the separator above which a
High Oil Separator
Shutdown
will be annunciated. The annunciation will only be triggered if the compressor is starting. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
3.
High Oil Separator Temperature Warning
This parameter is used to set an offset value subtracted from the
High Oil Separator Temperature Shutdown
Parameter. If the oil temperature exceeds this calculated value, a
High Oil Separator Temperature Warning
will be annunciated. The annunciation will only be triggered if the compressor is starting. The value is meas-
ured in the panel temperature units as selected on the
Panel Settings
screen.
4.
Low Oil Separator Temperature Shutdown
This parameter is used to select the temperature value in the separator below which a
Low Oil Separator
Temperature Shutdown
will be annunciated. The annunciation will only be triggered if the compressor is
starting. The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
5.
Low Oil Separator Temperature Warning
This parameter is used to set an offset value added to the
Low Oil Separator Temperature Shutdown
Param-
eter. If the oil temperature falls below this calculated value, a
Low Oil Separator Temperature Warning
will
be annunciated. The annunciation will only be triggered if the compressor is starting. The value is measured
in the panel temperature units as selected on the
Panel Settings
screen.
6.
High Oil Separator Level Shutdown Timer
This parameter is used to select the period of time for which the
High Oil Separator Level
input must remain
de-energized before a
High Oil Separator Level Shutdown
will be annunciated. This parameter is only visible
if the
Oil Level Max
option is selected in the level section of the
Configuration
. The value is measured in
seconds.
7.
High Oil Separator Level Warning Timer
This parameter is used to select the period of time for which the
High Oil Separator Level
input must remain
de-energized before a
High Oil Separator Level Warning
will be annunciated. This parameter is only visible if
the
Oil Level Max
option is selected in the level section of the
Configuration
. The value is measured in sec-
onds.
8.
Low Oil Separator Else Shutdown Timer
This parameter is used to select the period of time for which the
Oil Separator Low Level
input must remain
de-energized while the compressor is not stopped before a
Low Oil Separator Level Shutdown
will be
issued. This parameter is only visible if the
Oil Level Min
option is selected in the level section of the
Config-
uration
. The value is measured in seconds.
9.
Low Oil Separator Level Stop Shutdown Timer
This parameter is used to select the period of time for which the
Oil Separator Low Level
input must remain
de-energized while the compressor is stopped before a
Low Oil Separator Level Shutdown
will be issued.
This parameter is only visible if the
Oil Level Min
option is selected in the level section of the
Configuration
.
The value is measured in seconds.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
133