This option will cause the compressor to increase its capacity during the associated step.
–
Unload
This option will cause the compressor to decrease its capacity during the associated step.
–
Auto
This option will cause the compressor to automatically take steps to maintain a specific per-
cent capacity. The compressor will automatically load or unload to maintain the chosen
value during the associated step.
–
Hold
This option will cause the compressor to remain at a selected capacity during the associ-
ated step.
–
Standby
This option will cause the compressor to monitor all other compressors on the same level. If
any monitored compressor enters a shutdown state or cannot be started remotely, the com-
pressor will start. If multiple compressors are in standby mode at the same time, the com-
pressor that is most similar to the failed or inaccessible compressor will start.
6.
Control buttons
fig.54:
Sequencer Control Buttons
These buttons are used to control the operating mode sequencer. The buttons are:
a.
Auto
As long as this button is illuminated, the sequencer will run automatically based on the values
entered in the three timer columns.
b.
Hold
As long as this button is illuminated, the sequencer will remain on the currently selected step.
c.
Next
When this button is touched, the sequencer will immediately switch from the current step to the
next step below it in the table. If the sequencer is already on the final step, touching this button
will have no effect.
d.
Previous
When this button is touched, the sequencer will immediately switch from the current step to the
previous step above it in the table. If the sequencer is already on the first step, touching this
button will have no effect.
Instruction Manual | GEA Omni™
Control panel
User interface
Sequencer
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
57