Parameter
Units
Minimum
Maximum
Default
kg/cm²G
0.00 kg/cm²D
2.11 kg/cm²D
0.00 kg/cm²D
kg/cm²A
1.
Wet Bulb Set Point Split
This parameter is used to select the value that will be added to the calculated ideal saturated discharge
pressure to obtain the floating set point. The value is measured in the panel pressure units as selected on
the
Panel Settings
screen.
3.3.3
Discharge Pressure
Parameter
Units
Minimum
Maximum
Default
High Discharge Pressure Warning
barG
5.17 barG
24.13 barG
12.06 barG
barA
6.18 barA
25.14 barA
13.08 barA
PSIG
75.0 PSIG
350.0 PSIG
160.3 PSIG
PSIA
89.6 PSIA
364.6 PSIA
189.6 PSIA
kPaG
517 kPaG
2413 kPaG
1206 kPaG
kPaA
618 kPaA
2514 kPaA
1306 kPaA
MPaG
0.517 MPaG
2.413 MPaG
1.206 MPaG
MPaA
0.618 MPaA
2.514 MPaA
1.308 MPaA
kg/cm²G
5.27 kg/cm²G
24.61 kg/cm²G
12.30 kg/cm²G
kg/cm²A
6.30 kg/cm²A
25.64 kg/cm²A
13.33 kg/cm²A
High Discharge Pressure Warning
Delay
Seconds
0 s
30 s
0 s
Low Discharge Pressure Warning
barG
-1.01 barG
24.13 barG
8.27 barG
barA
0.00 barA
25.14 barA
9.28 barA
PSIG
-29.9 PSIG
350.0 PSIG
105.3 PSIG
PSIA
0.00 PSIA
364.6 PSIA
134.6 PSIA
Instruction Manual | GEA Omni™
Control panel
Control
Condenser Sequencer Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
159