6.
Low Motor Speed Shutdown
This parameter is used to set the motor speed value below which a
Low Motor Speed Shutdown
will be
annunciated. This parameter is only visible if the configuration indicates that the compressor is equipped
with a variable speed motor and a separate motor speed input. The value is measured in rpm.
7.
Motor Speed Maximum
This parameter is used to set the speed the motor will run at when the speed reference analog output is set
to 20 mA. This parameter will only be visible if the configuration indicates that the compressor uses a varia-
ble speed motor. The value is measured in rpm.
8.
Motor Speed Minimum
This parameter is used to set the speed the motor will run at when the speed reference analog output is set
to 4 mA. This parameter will only be visible if the configuration indicates that the compressor uses a variable
speed motor. The value is measured in rpm.
3.1.9
Motor Temperature
Parameter
Units
Minimum
Maximum
Default
High Motor Bearing Shutdown
°C
0.0 °C
200.0 °C
100.0 °C
°F
32.0 °F
392.0 °F
212.0 °F
High Motor Bearing Warning Offset
Kelvin
0.0 K
50.0 K
10.0 K
°F
0.0 °F
90.0 °F
18.0 °F
High Motor Winding Shutdown
°C
0.0 °C
200.0 °C
100.0 °C
°F
32.0 °F
392.0 °F
212.0 °F
High Motor Winding Warning Offset
Kelvin
0.0 K
50.0 K
10.0 K
°F
0.0 °F
90.0 °F
18.0 °F
1.
High Motor Bearing Shutdown
This parameter is used to select the temperature value in the either motor bearing above which a high tem-
perature shutdown condition will be annunciated. This parameter will only be visible if motor bearing temper-
ature monitoring is selected in the
Motor Temperature Safeties
field motor section of the configuration. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
2.
High Motor Bearing Warning Offset
This parameter is used to set an offset value subtracted from the
High Motor Bearing Shutdown
parameter.
If the temperature on either motor bearing exceeds this calculated value, a high temperature warning condi-
tion will be annunciated. This parameter will only be visible if motor bearing temperature monitoring is
selected in the
Motor Temperature Safeties
field motor section of the configuration. The value is measured in
the panel temperature units as selected on the
Panel Settings
screen.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
120
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016