Shutdown
Explanation
Oil Pump 2 Illegal Interlock
Shutdown
This annunciation will be triggered if the interlock input of the lag oil pump in
a dual pump system becomes energized while the lag pump start output is
de-energized. This annunciation will only be enabled if the compressor is
configured with dual oil pumps.
Oil Pump Loss of Interlock
Shutdown
This annunciation will be triggered if the oil pump interlock input becomes de-
energized while the oil pump start output is energized.
High Oil Separator Level Shut-
down
This annunciation will be triggered if the level in the oil separator remains
above the high level float switch for a period of time greater than the
High Oil
Separator Shutdown Timer
parameter.
Compressor Illegal Interlock
Shutdown
This annunciation will be triggered if the compressor run status input
becomes energized while the compressor start output is de-energized.
Illegal Compressor Motor Cur-
rent Shutdown
This annunciation will be triggered if the motor current of the compressor is
higher than the percentage of the motor FLA as indicated by the value of the
Illegal Compressor Motor Current Shutdown
while compressor should be
stopped.
Compressor Loss of Compres-
sor Interlock
This annunciation will be triggered if the compressor run status input
becomes de-energized while the compressor start output is energized.
Low Suction Superheat Shut-
down
This annunciation will be triggered if the calculated suction superheat value
falls below the value of the
Low Suction Superheat Shutdown
parameter.
This shutdown will only be issued if superheat annunciations have been ena-
bled through the
Superheat Annunciations
parameter.
High Suction Superheat Shut-
down
This annunciation will be triggered if the calculated suction superheat value
exceeds the value of the
High Suction Superheat Shutdown
parameter. This
shutdown will only be issued if superheat annunciations have been enabled
through the
Superheat Annunciations
parameter.
Low Discharge Superheat Shut-
down
This annunciation will be triggered if the calculated suction superheat value
falls below the value of the
Low Discharge Superheat Shutdown
parameter.
This shutdown will only be issued if superheat annunciations have been ena-
bled through the
Superheat Annunciations
parameter.
High Discharge Superheat
Shutdown
This annunciation will be triggered if the calculated discharge superheat
value falls below the value of the
High Discharge Superheat Shutdown
parameter. This shutdown will only be issued if superheat annunciations
have been enabled through the
Superheat Annunciations
parameter.
Instruction Manual | GEA Omni™
Control panel
Annunciations
Shutdowns