Shutdown
Explanation
High Oil Separator Tempera-
ture Shutdown
This annunciation will be triggered if the oil separator temperature reading
exceeds the value of the
High Oil Separator Temperature Shutdown
parame-
ter. This shutdown will only be annunciated if the compressor is in the start-
ing or running states.
Low Oil Separator Temperature
Shutdown
This annunciation will be triggered if the oil separator temperature reading
falls below the value of the
Low Oil Separator Temperature Shutdown
parameter. This shutdown will only be annunciated if the compressor is in the
starting or running states.
Low Oil Level Shutdown
This annunciation will be triggered if the
Low Oil Level Input
becomes de-
energized for a period of time in excess of the value entered in the
Low Oil
Level Shutdown Timer
.
High Oil Temperature Shut-
down
This annunciation will be triggered if the oil temperature reading exceeds the
value of the
High Oil Temperature Shutdown
parameter. This shutdown will
only be annunciated if the compressor is in the starting or running states.
Low Oil Temperature Shutdown This annunciation will be triggered if the oil temperature reading falls below
the value of the
Low Oil Temperature Shutdown
parameter. This shutdown
will only be annunciated if the compressor is in the starting or running states.
High Oil Differential Pressure
Shutdown
This annunciation will be triggered if the oil differential pressure reading
exceeds the value of the
High Oil Differential Pressure Shutdown
parameter.
This shutdown will only be annunciated if the compressor is in the starting or
running states.
Low Oil Differential Pressure
Shutdown
This annunciation will be triggered if the oil differential pressure reading falls
below the value of the
Low Oil Differential Pressure Shutdown
parameter.
This shutdown will only be annunciated if the compressor is in the starting or
running states.
High Oil Filter Differential Shut-
down
This annunciation will be triggered if the oil filter differential pressure reading
exceeds the value of the
High Oil Filter Differential Pressure Shutdown
parameter. This shutdown will only be annunciated if the compressor is in the
starting or running states.
Oil Pump Illegal Interlock Shut-
down
This annunciation will be triggered if the oil pump interlock input becomes
energized while the oil pump start output is de-energized..
Oil Pump 1 Illegal Interlock
Shutdown
This annunciation will be triggered if the interlock input of the lead oil pump in
a dual pump system becomes energized while the lead pump start output is
de-energized. This annunciation will only be enabled if the compressor is
configured with dual oil pumps.
Annunciations
Shutdowns
Instruction Manual | GEA Omni™
Control panel
208
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016