7.
Limitation Outlet Temperature Load Inhibit
This parameter is used to set an offset value added to the
Low Outlet Temperature Shutdown
parameter. If
the Outlet Temperature falls below this calculated value, the compressor will be prevented from loading. The
parameter will only be visible if the control signal of the compressor is currently set to
Outlet Temperature
.
The value is measured in the panel temperature units as selected on the
Panel Settings
screen.
8.
Limitation Outlet Temperature Force Unload
This parameter is used to set an offset value added to the
Low Outlet Temperature Shutdown
parameter. If
the outlet temperature falls below this calculated value, the compressor will be forced to unload. The param-
eter will only be visible if the control signal of the compressor is currently set to
Outlet Temperature
. The
value is measured in the panel temperature units as selected on the
Panel Settings
screen.
3.1.22
Loss of Remote Start Signal
Parameter
Units
Minimum
Maximum
Default
Loss of Remote Start Signal Run
Warning Timer
Seconds
0 s
120 s
20 s
1.
Loss of Remote Start Signal Run Warning Timer
This parameter is only used if the compressor was manually started and then switched to remote mode. A
start command must be received from a sequencer within the period of time selected here or a
Loss of
Remote Start Signal
warning will be annunciated. The value is measured in seconds.
3.1.23
Power Failure Restart
Parameter
Units
Minimum
Maximum
Default
Power Failure Restart Mode
Selection – See Description
Power Failure Restart Delay
Seconds
0 s
8000 s
10 s
Power Failure Restart Abort Timer
Minutes
0.0 min
480.0 min
10.0 min
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
147