Parameter
Units
Minimum
Maximum
Default
kg/cm²G
1.02 kg/cm²D
kg/cm²A
High Oil Differential Pressure Start-
ing Shutdown Timer
Seconds
0 s
900 s
See Description
High Oil Differential Pressure Run-
ning Shutdown Timer
Seconds
0 s
900 s
See Description
High Oil Differential Pressure
Warning Offset
barG
0.10 barD
10.00 barD
0.25 barD
barA
PSIG
1.5 PSID
145.0 PSID
3.6 PSID
PSIA
kPaG
10 kPaD
1000 kPaD
25 kPaD
kPaA
MPaG
0.010 MPaD
1.000 MPaD
0.025 MPaD
MPaA
kg/cm²G
0.10 kg/cm²D
10.20 kg/cm²D
0.25 kg/cm²D
kg/cm²A
High Oil Differential Pressure
Warning Timer
Seconds
0 s
600 s
See Description
Low Oil Differential Pressure Shut-
down
barG
-3.00 barD
10.00 barD
See Description
barA
PSIG
-43.5 PSID
145.0 PSID
PSIA
kPaG
-300 kPaD
1000 kPaD
kPaA
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
127
Содержание Omni
Страница 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Страница 238: ......