This parameter is used to select the capacity slide valve position above which Capacity Output 2 should be
energized.
4.
Capacity Output 2 Off
This parameter is used to select the capacity slide valve position below which Capacity Output 2 should be
de-energized.
5.
Slide Or Capacity Selection
This parameter is used to select whether the capacity analog output point transmits the current capacity per-
centage of the compressor or the percentage of its maximum travel. The options are:
•
Capacity
•
Percent of Max Travel
3.1.28
VTrac
Parameter
Units
Minimum
Maximum
Default
Causes Shutdown
Selection – See Description
Disable VTrac Notifications Below
Capacity Slide
Percent
0 %
100 %
0 %
1.
Causes Shutdown
This parameter is used to select the type of annunciation that will be triggered by the VTrac. The parameter
will only be visible if the compressor is configured for VTrac monitoring The options are:
•
Warning
•
Shutdown
2.
Disable VTrac Notifications Below Capacity Slide
This parameter is used to select the Slide valve position below which the VTrac will not trigger warnings or
shutdowns. The parameter will only be visible if the compressor is configured for VTrac monitoring. The
value is measured in percent.
3.1.29
Compressor Service
Parameter
Units
Minimum
Maximum
Default
Compressor Service Notification
Selection – See Description
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
154
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016