SENSOR CALIBRATION
All sensors providing data to the GEA Omni™ panel may be calibrated from the
Sensors
tab of the
Configuration
screen. For more information Section 2.14.2, Page 96.
GEA recommends that transducer calibrations be checked annually.
5.1
Pressure Transducer Calibration
1. Ensure that the control panel is in
Service Mode
and the compressor is
Stopped
.
2. Touch the cell associated with the
Measured
value of the sensor in question to bring up the calibration
pad shown below.
fig.115:
Pressure Sensor Calibration Pad
3. Attach a calibrated gauge or digital multimeter attachment to the service valve of the transducer.
4. Remove the cover and open the service valve.
5. Record the actual pressure on the gauge or multimeter.
6. Use the keypad to enter the recorded value for the sensor. Maximum and minimum limits will be set
automatically by taking the current reading and respectively adding and subtracting ten percent of the
transducer’s range.
•
Maximum and minimum values are displayed at the bottom of the keypad display. If the recorded
value falls outside these bounds, it is an indication that the transducer may be damaged, incorrectly
wired or of the wrong type.
7. Complete calibration for the sensor by touching the
Enter
button.
Instruction Manual | GEA Omni™
Control panel
Sensor Calibration
Pressure Transducer Calibration
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
225