Oil System Details
fig.107:
Oil system details options
1.
Oil Pump
This drop down list is used to select the type of oil pump on the package.
2.
Oil Pressure Location
This drop down list is used to select the location where the oil pressure is measured. This option is only
available on GEA compressors. This option may not be modified in the field.
3.
Oil Cooling
This drop down list is used to select the type of oil cooling on the package.
4.
Oil Drain Minimum Timer
This text box is used to enter the minimum amount of time, measured in minutes, that the compressor
must remain off after the oil pump is stopped before it is allowed to start again.
5.
Oil Differential Pressure Max
This text box is used to enter the maximum value for the oil differential pressure parameters. The value
is entered in PSID.
Filter
This section is a subsection of the oil system. It contains four individual fields relating to the operation of the oil
filter.
Instruction Manual | GEA Omni™
Control panel
Control
Configuration
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016