2.5
Compressor
The
Compressor
menu is used to control each compressor from the panel. There are multiple tabs which are
detailed below. The bottom of the screen contains the eight standard buttons used to control the compressor.
Active buttons are illuminated with black text and a white outline while inactive buttons are darkened with white
text.
fig.22:
Standard compressor buttons
The buttons are:
1.
STOP
This button is illuminated whenever the compressor is in the stopped state, whether through a normal
stoppage or through a shutdown condition. Touching this button will initiate the stopping procedure. For
more information, refer to Section 3.9.4, Page 198. While the compressor is in the stopping process, this
button will flash. Touching the button a second time will cause the compressor to stop without unloading.
2.
START
This button is illuminated whenever the compressor is running in local mode. Touching this button will
attempt to start the compressor. If the compressor is in the process of starting, this button will flash.
Once the compressor has started, the button will be illuminated continuously. If the compressor is in
Automatic Start/Stop
mode, this button will display an
A
in its upper left hand corner and will resume
flashing if it has been automatically stopped to allow pressure to build.
3.
REMOTE
This button is illuminated whenever the compressor is set to receive instructions from an external
source, such as a sequencer. Touching this button will switch the compressor from local to remote con-
trol.
4.
AUTO
This button is illuminated whenever the compressor is set to control its capacity automatically based on
the control signal. Touching the button will switch the compressor to
Automatic
mode.
Instruction Manual | GEA Omni™
Control panel
User interface
Compressor
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
29