4.
Dead Band
This parameter is used to define a range above and below the set point within which no capacity control
adjustments will be made. This functionality is illustrated in the Figure 113, Page 200 and Figure 114,
Page 201. The maximum value, minimum value and units of the parameter are dependent on the chosen
control signal:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
5.
Proportional Band
This parameter is used to define a range above and below the set point within which the width of the
capacity control pulses is reduced to avoid overshooting or undershooting the set point. This functionality is
illustrated in the Figure 113, Page 200 and Figure 114, Page 201. The maximum value, minimum value and
units of the parameter are dependent on the chosen control signal:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
6.
Automatic Start Stop
This parameter is used to select whether the panel is permitted to run and stop the compressor automatically
to maintain the control signal. While the parameter is not set to
Disabled
, an
A
will appear in the upper left
hand corner of the
Start
button.
The options are:
•
Disabled
•
Offsets
•
Set points
7.
Automatic Start
This parameter is used to select the control signal value at which the compressor will attempt to start. This
parameter is only visible if the
Automatic Start Stop
parameter is set to
Set points
. The maximum value, min-
imum value and units of the parameter are dependent on the chosen
Control Signal
:
•
Pressure
Measured in the panel pressure units as selected in the
Panel Settings
screen.
•
Temperature
Measured in the panel temperature units as selected in the
Panel Settings
screen.
•
Remote Capacity Slide
Measured in percent.
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
106
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016