3.
Previous Step
This parameter is used to select the amount that the control signal must deviate from the Set Point before
the sequencer will begin the process of switching to the previous step in the schedule. The maximum value,
minimum value and units of the parameter are dependent on the chosen control signal.
•
Discharge Pressure or Wet Bulb
Measured in the panel pressure units as selected in the Panel Settings screen.
•
Condenser Control Temperature
Measured in the panel temperature units as selected in the Panel Settings screen.
4.
Next Step
This parameter is used to select the amount that the control signal must deviate from the Set Point before
the sequencer will begin the process of switching to the next step in the schedule. The maximum value, mini-
mum value and units of the parameter are dependent on the chosen control signal.
•
Discharge Pressure or Wet Bulb
Measured in the panel pressure units as selected in the Panel Settings screen.
•
Condenser Control Temperature
Measured in the panel temperature units as selected in the Panel Settings screen.
3.3.2
Wet Bulb Control
Hint!
This section will only appear if at least one of the schedules has Wet Bulb selected as its con-
trol signal.
Parameter
Units
Minimum
Maximum
Default
Wet Bulb Set Point Split
barG
0.00 barD
2.07 barD
0.00 barD
barA
PSIG
0.00 PSID
30.0 PSID
0.00 PSID
PSIA
kPaG
0.00 kPaD
207 kPaD
0.00 kPaD
kPaA
MPaG
0.00 MPaD
0.207 MPaD
0.00 MPaD
MPaA
Control
Condenser Sequencer Control Parameters
Instruction Manual | GEA Omni™
Control panel
158
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016