Parameter
Units
Minimum
Maximum
Default
PSIA
0.0 PSIA
145.0 PSIA
109.7 PSIA
kPaG
-101 kPaG
899 kPaG
655 kPaG
kPaA
0 kPaA
1000 kPaA
756 kPaA
MPaG
-0.101 MPaG
0.899 MPaG
0.655 MPaG
MPaA
0.000 MPaA
1.000 MPaA
0.756 MPaA
kg/cm²G
759.8 mmHg
9.16 kg/cm²G
6.68 kg/cm²G
kg/cm²A
0.00 kg/cm²A
10.20 kg/cm²A
7.01 kg/cm²A
Oil Pump Lead Selection
Selection – See Description
Oil Pump Maintained Timer
Seconds
0 s
300 s
2 s
Oil Pump Circulation Mode
Selection – See Description
Oil Pump Circulation Temperature
Set Point
°C
0.0 °C
50.0 °C
10.0 °C
°F
32.0 °F
122.0 °F
50.0 °F
Oil Pump Circulation Shutdown
Timer
Seconds
0 s
600 s
120 s
Time Between Oil Pump Circulation
Hours
0 h
500 h
4 h
Duration of Oil Pump Circulation
Minutes
0 min
500 min
4 min
1.
Oil Pump 1 Runtime
This parameter is used to display the total accumulated runtime of the first oil pump. The value is measured
in hours.
2.
Oil Pump 2 Runtime
This parameter is used to display the total accumulated runtime of the second oil pump. This parameter will
only be visible if dual oil pump control is enabled in the
Oil System Details
section of the configuration. The
value is measured in hours.
3.
Oil Pump Start Attempts
This parameter is used to select the number of times the oil pump will attempt to start to build oil pressure. If
this number is exceeded, a
Low Oil Differential Shutdown
will be annunciated. This parameter will only be
enabled if the compressor
brand
is set to Grasso.
Instruction Manual | GEA Omni™
Control panel
Control
Compressor Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016