Parameter
Units
Minimum
Maximum
Default
Pump Down Cycle Off Set Point
barG
-1.01 barG
98.99 barG
-1.01 barG
barA
0.00 barA
100.00 barA
0.00 barA
PSIG
29.9 inHg
1435.7 PSIG
29.9 inHg
PSIA
0.0 PSIA
1450.4 PSIA
0.0 PSIA
kPaG
-101 kPaG
9899 kPaG
-101 kPaG
kPaA
0 kPaA
10000 kPaA
0 kPaA
MPaG
-0.101 kPaG
9.899 kPaG
-0.101 kPaG
MPaA
0.000 kPaA
10.000 kPaA
0.000 kPaA
kg/cm²G
759.8 mmHg
100.94 kg/cm²G
759.8 mmHg
kg/cm²A
0.00 kg/cm²A
101.98 kg/cm²A
0.00 kg/cm²A
Pump Down Max Cycle Attempts
Unitless
0
100
0
Pump Down Max Cycle Period
Hours
0.00 h
20.00 h
0.00 h
Second Liquid Feed On Above
Capacity
Percent
0 %
100 %
50 %
Second Liquid Feed Off Below
Capacity
Percent
0 %
100 %
45 %
1.
Compressor Start Pressure
This parameter is used to select the value that the suction pressure must exceed after the liquid feed valve is
opened during the compressor start process. Motor start will be delayed until this condition is met. The value
is measured in the currently selected pressure units of the panel.
2.
Pump Down Maximum Time
This parameter is used to select the maximum amount of time that the panel will be permitted to run in pump
down mode before a shutdown will be annunciated.
3.
Pump Down Count
This parameter is used to select whether the pump down process will run any time the suction pressure
exceeds the
Pump Down Cycle On Set Point
, or if it will only execute a single time. The options are:
•
Continuous
•
Once
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
152
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016