Parameter
Units
Minimum
Maximum
Default
Control Mode After Shutdown
Selection – See Description
Sequencer Control
Selection – See Description
1.
Control Mode
This parameter is used to select which set of
Capacity Control
parameters is used by the panel. Whichever
set of parameters is selected here will be the visible set shown in the
Capacity Control
section above. This
parameter will only be visible if
Control Mode Select By Digital Input
is set to
Disabled
. The options are:
•
Capacity Control 1
•
Capacity Control 2
•
Capacity Control 3
2.
Control Mode Select By Digital Input
This parameter is used to select whether the capacity control mode is selected using a parameter or a Digital
Input point. If a Digital Input point is used, the compressor will be limited to Capacity Control 1 on a de-ener-
gized signal, and Capacity Control 2 on an energized signal. The parameter will only be visible if the
Set
Point Selection Digital Input
option is enabled in the panel configuration. The options are:
•
Enabled
•
Disabled
3.
Set Point Location
This parameter is used to select whether the capacity control set point is taken from the selected set of
Capacity Control
parameters or from a
Remote
device. The options are:
•
Local
•
Remote
4.
Remote Set Point Units
This parameter is used to select the units of measurement that will be used for remote set point control. The
parameter will only be visible if the
Remote Set Point
option is enabled in the panel configuration. The
options are:
•
Pressure
•
Temperature
•
Slide Valve
Control
Compressor Control Parameters
Instruction Manual | GEA Omni™
Control panel
110
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016