1.
Viewable Grid Area
From here, the user can view the annunciation table. The table is divided into seven columns as detailed
below.
•
Type
The graphic displayed here is determined by the type of the triggered annunciations. Red indicates shut-
down, yellow indicates warning and blue indicates a notification.
•
Description
Displays the name of the annunciation that was triggered.
•
Time
The time when the annunciation was either issued or cleared.
•
Parameter
The current value of the warning or shutdown set point which triggered the annunciation, where applica-
ble.
•
Action
The text displayed here indicates whether the annunciation was issued or cleared.
•
Clear
This column will be filled only if the action column displays
Cleared
. It indicates whether the annunciation
was cleared manually or automatically.
•
RT-Trend
When a shutdown or warning annunciation is issued, the last fifteen minutes of historical data is
recorded. The user may view this information by selecting the picture embedded into the grid’s cell.
These will not be generated during panel startup. Manual RT-Trend snapshots are also displayed in this
format and appear in the table as notifications.
Instruction Manual | GEA Omni™
Control panel
User interface
History
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
67
Содержание Omni
Страница 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Страница 238: ......