manualshive.com logo in svg
background image

IM05805004K

Effective January 2003

             Instructions for Cutler-Hammer
   

         Jockey Pump Controllers

IM05805004K

Содержание Cutler-Hammer Jockey

Страница 1: ...IM05805004K Effective January 2003 Instructions for Cutler Hammer Jockey Pump Controllers IM05805004K...

Страница 2: ......

Страница 3: ...1 ELECTRICAL CHECKOUT INSTRUCTIONS 2 3 1 1 Motor Rotation Check 2 3 1 2 Pressure Switch Set Point 2 3 1 3 Starting and Stopping 2 3 1 4 Overload Relay Trip Setting 2 3 1 5 Running Period Timer Optiona...

Страница 4: ......

Страница 5: ...bottom external side of the enclosure The connection should be installed as per NFPA pamphlet No 20 NOTE Water lines to the pressure switch must be free from dirt and contamination The pressure should...

Страница 6: ...structions These instructions check out automatic starting and stopping 3 1 3 Starting and Stopping Energize the controller With the H O A selector switch set to AUTO if the system water pressure is l...

Страница 7: ...pump starting pressure Turn the Range Adjusting Screw clockwise to reduce the pressure and observe the scale on the switch 2 Bleed the fire protection water system until the pressure is reduced to the...

Страница 8: ...IM05805004K Effective January 2003 Page 4 FIGURE 1...

Страница 9: ...IM05805004K Effective January 2003 FIGURE 2 Page 5...

Страница 10: ...IM05805004K Effective January 2003 FIGURE 3 Page 6...

Страница 11: ...IM05805004K Effective January 2003 Page 7...

Страница 12: ...er Hammer 403 East Lake Blvd Airdrie Alberta T4A 2G1 Canada tel 403 948 7955 fax 403 948 6967 www chfire com 2003 Eaton Corporation All Rights Reserved Printed in Canada Publication No IM05805004K Jan...

Отзывы: