Drive set-up procedure
14.1.6 External encoder
14-24
• MD3211 (Pn20B) PG_PLS_MTRRND_HW_FULLCLOSED (For each axis)
Meaning:
The number of full-closed PG pulses/Single revolution of motor
(Upper word)
Setting value: [Pulse]
Note: Set MD3210 and MD3211 to a 1-multiplication value.
• MD3212 (Pn20C) PG_PLS_ENCRND_LW_FULLCLOSED (For each axis)
Meaning:
The number of full-closed PG pulses/Single revolution of encoder
(Lower word)
Setting value: [Pulse]
• MD3213 (Pn20D) PG_PLS_ENCRND_HW_FULLCLOSED (For each axis)
Meaning:
The number of full-closed PG pulses/Single revolution of encoder
(Upper word)
Setting value: [Pulse]
Note: Set MD3212 and MD3213 to a 1-multiplication value.
• MD3231 (Pn21F) PG_PLS_ENCRND_Z_PHASE (For each axis)
Meaning:
The number of Z-phase pulses/Single revolution of encoder.
When Mitsubishi Heavy Industries MP scale is used, this value must be
set.
Setting value: [Pulse]
• MD3508 (Pn808) ABS_PG_POINT_OFFS_LW (For each axis)
Meaning:
Absolute PG zero offset (Lower word)
When Mitsubishi Heavy Industries MP scale is used, this value must be
set to an offset amount from motor encoder.
Setting value: [Pulse]
• MD3509 (Pn809) ABS_PG_POINT_OFFS_HW (For each axis)
Meaning:
Absolute PG zero offset (Upper word)
When Mitsubishi Heavy Industries MP scale is used, this value must be
set to an offset amount from motor encoder.
Setting value: [Pulse]
Summary of Contents for CNC Series
Page 1: ...Maintenance Manual Serviceman Handbook MANUAL No NCSIE SP02 19 Yaskawa Siemens CNC Series...
Page 26: ...Part 1 Hardware...
Page 38: ...System Configuration 1 2 3 Spindle motor designations 1 12...
Page 58: ...Installing the control panels 2 3 5 Installing lightning surge absorbers 2 20...
Page 62: ...Installing the motors 3 4...
Page 84: ...Connection method 4 3 2 Setting the rotary switches on the inverters and servo units 4 22...
Page 96: ...Part 2 Software...
Page 102: ...Software configuration 6 6...
Page 113: ...7 2 Network settings 7 11 8 Click on the radio button to the left of Specify an IP address...
Page 121: ...7 2 Network settings 7 19...
Page 122: ...Part 3 PLC...
Page 154: ...Part 4 Setting up and maintenance...
Page 160: ...Overview of System 10 1 2 Basic operation 10 6...
Page 204: ...How to use Digital Operation 12 2 9 Setting the password setting for write prohibit 12 32...
Page 327: ...Error and Troubleshooting 15 4...
Page 328: ...15 1 Errors without Alarm Display and Troubleshooting 15 5...
Page 329: ...Error and Troubleshooting 15 6...
Page 343: ...Maintenance and Check 16 3 3 Setting up Initializing Absolute encoder 16 14...