M800/M80/E80/C80 Series Alarm/Parameter Manual
10 User PLC Alarms (U)
114
IB-1501279-H
Details
Maximum project No. illegal (at PLC system startup)
Multi-project parameter setting is illegal (due to the following reason).
The value outside the setting range (1 to number of usable project) was detected.
Remedy
(1) Check the presence of the expansion project additional specification and reconsider the setting range.
(2) The multi-project parameter (maximum project No.) setting is illegal. Set the multi-project parameter again.
(3) If (1) or (2) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsub-
ishi.
Details
Project ratio illegal
Multi-project parameter setting is illegal (due to the following reason).
It was detected that the total of ratios of all projects was outside the range from 0 to 100.
Remedy
(1) The multi-project parameter (project ratio) setting is illegal. Set the multi- project parameter again.
(2) If (1) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsubishi.
Details
Temporary memory area over (at the PLC system startup)
Multi-project parameter setting is illegal (due to the following reason).
The ratio to which the area after the project ratio setting is smaller than the size of ladder stored in the
temporary memory area was detected.
Remedy
(1) Check the presence of the large-capacity PLC additional specification and reconsider the size that can be
stored.
(2) The multi-project parameter (project ratio) setting is illegal. Set the multi- project parameter again.
(3) If (1) or (2) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsub-
ishi.
Details
Built-in ROM area over (at the PLC system startup)
Multi-project parameter setting is illegal (due to the following reason).
The ratio to which the area after the project ratio setting is smaller than the size of ladder stored in the built-
in ROM area was detected.
Remedy
(1) Check the presence of the large-capacity PLC additional specification and reconsider the size that can be
stored.
(2) The multi-project parameter (project ratio) setting is illegal. Set the multi- project parameter again.
(3) If (1) or (2) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsub-
ishi.
Details
Comment area over (at the PLC system startup)
Multi-project parameter setting is illegal (due to the following reason).
The ratio to which the area after the project ratio setting is smaller than the size of comment and message
stored in the built-in ROM area.
Remedy
(1) The multi-project parameter (project ratio) setting is illegal. Set the multi- project parameter again.
(2) If (1) does not solve the problem, there is a possibility that the NC system is broken. Contact Mitsubishi.
U10
Illegal PLC
0x500*
-
U10
Illegal PLC
0x510*
-
U10
Illegal PLC
0x520*
-
U10
Illegal PLC
0x530*
-
U10
Illegal PLC
0x540*
-
Summary of Contents for C80 Series
Page 1: ......
Page 7: ......
Page 11: ......
Page 13: ......
Page 15: ......
Page 18: ...1 IB 1501279 H Alarm ...
Page 19: ...M800 M80 E80 C80 Series Alarm Parameter Manual 2 IB 1501279 H ...
Page 20: ...1 3 IB 1501279 H Operation Errors M ...
Page 54: ...2 37 IB 1501279 H Stop Codes T ...
Page 62: ...3 45 IB 1501279 H Servo Spindle Alarms S ...
Page 81: ...M800 M80 E80 C80 Series Alarm Parameter Manual 3 Servo Spindle Alarms S 64 IB 1501279 H ...
Page 82: ...4 65 IB 1501279 H MCP Alarms Y ...
Page 98: ...5 81 IB 1501279 H System Alarms Z ...
Page 111: ...M800 M80 E80 C80 Series Alarm Parameter Manual 5 System Alarms Z 94 IB 1501279 H ...
Page 112: ...6 95 IB 1501279 H Absolute Position Detection System Alarms Z7 ...
Page 118: ...7 101 IB 1501279 H Distance coded Reference Scale Errors Z8 ...
Page 120: ...8 103 IB 1501279 H Emergency Stop Alarms EMG ...
Page 124: ...9 107 IB 1501279 H Computer Link Errors L ...
Page 126: ...10 109 IB 1501279 H User PLC Alarms U ...
Page 136: ...11 119 IB 1501279 H Network Service Errors N ...
Page 139: ...M800 M80 E80 C80 Series Alarm Parameter Manual 11 Network Service Errors N 122 IB 1501279 H ...
Page 140: ...12 123 IB 1501279 H Program Errors P ...
Page 178: ...13 161 IB 1501279 H Smart Safety Observation Alarm V ...
Page 192: ...14 175 IB 1501279 H Multi CPU Errors A C80 ...
Page 215: ...M800 M80 E80 C80 Series Alarm Parameter Manual 14 Multi CPU Errors A C80 198 IB 1501279 H ...
Page 216: ...199 IB 1501279 H Parameter ...
Page 217: ...M800 M80 E80 C80 Series Alarm Parameter Manual 200 IB 1501279 H ...
Page 218: ...15 201 IB 1501279 H User Parameters ...
Page 359: ...M800 M80 E80 C80 Series Alarm Parameter Manual 15 User Parameters 342 IB 1501279 H ...
Page 360: ...16 343 IB 1501279 H Machine Parameters ...
Page 748: ......