M800/M80/E80/C80 Series Alarm/Parameter Manual
1 Operation Errors (M)
9
IB-1501279-H
Details
The axis travel command is interlocked as the tap retract is being enabled.
Remedy
If tapping is necessary, perform tapping retract in advance. However, tapping retract is not allowed during
cycle start operation. Carry out tapping retract after resetting.
If tapping is not necessary, cancel the tap retract enabled condition by the tap retract enabled cancel sig-
nal.
Details
The handle ratio is too large for the handle feed clamp speed.
(The handle feed clamp speed changes according to the rapid traverse rate, external feedrate, maximum
speed outside the soft limit range and etc. (or external deceleration speed when external deceleration is valid))
Too large handle ratio means the ratio with which the machine is unable to move the distance of [iunit * handle
ratio] within 0.1ms at the clamp speed.
Example)
When iunit=B (0.001mm) and clamp speed cs (mm/min)
The operation error (M01 0060) will occur if
ratio M>cs/60(s)*0.1(ms)/0.001(mm)=cs*10/6.
Remedy
Change the settings of the handle feed clamp speed or the handle ratio.
Details
At the start of reference position initial setting, the parameter "#2034 rfpofs" (Distance-coded reference position
detection offset) is not set to "0".
Remedy
Set the parameter "#2034 rfpofs" to "0", then turn the power ON again to perform the reference position
initial setting.
Details
Reference position could not be established within the maximum scan distance.
Remedy
Check the scale to see if it has dirt or damage.
Check if the servo drive unit supports this function.
Details
One of the following operations was attempted during workpiece installation error compensation.
Manual interruption
Automatic operation handle interruption
MDI interruption
PLC interruption
Remedy
Return the operation mode to the original mode to remove the cause. During workpiece installation error
compensation, manual interruption, automatic operation handle interruption, MDI interruption, PLC inter-
ruption, etc. is not allowed.
M01
Wait for tap retract
0057
M01
Handle ratio too large
0060
M01
R-pos offset value illegal
0065
M01
R-pos scan distance exceeded
0066
M01
Illegal op in wk instl err cmp
0070
Summary of Contents for C80 Series
Page 1: ......
Page 7: ......
Page 11: ......
Page 13: ......
Page 15: ......
Page 18: ...1 IB 1501279 H Alarm ...
Page 19: ...M800 M80 E80 C80 Series Alarm Parameter Manual 2 IB 1501279 H ...
Page 20: ...1 3 IB 1501279 H Operation Errors M ...
Page 54: ...2 37 IB 1501279 H Stop Codes T ...
Page 62: ...3 45 IB 1501279 H Servo Spindle Alarms S ...
Page 81: ...M800 M80 E80 C80 Series Alarm Parameter Manual 3 Servo Spindle Alarms S 64 IB 1501279 H ...
Page 82: ...4 65 IB 1501279 H MCP Alarms Y ...
Page 98: ...5 81 IB 1501279 H System Alarms Z ...
Page 111: ...M800 M80 E80 C80 Series Alarm Parameter Manual 5 System Alarms Z 94 IB 1501279 H ...
Page 112: ...6 95 IB 1501279 H Absolute Position Detection System Alarms Z7 ...
Page 118: ...7 101 IB 1501279 H Distance coded Reference Scale Errors Z8 ...
Page 120: ...8 103 IB 1501279 H Emergency Stop Alarms EMG ...
Page 124: ...9 107 IB 1501279 H Computer Link Errors L ...
Page 126: ...10 109 IB 1501279 H User PLC Alarms U ...
Page 136: ...11 119 IB 1501279 H Network Service Errors N ...
Page 139: ...M800 M80 E80 C80 Series Alarm Parameter Manual 11 Network Service Errors N 122 IB 1501279 H ...
Page 140: ...12 123 IB 1501279 H Program Errors P ...
Page 178: ...13 161 IB 1501279 H Smart Safety Observation Alarm V ...
Page 192: ...14 175 IB 1501279 H Multi CPU Errors A C80 ...
Page 215: ...M800 M80 E80 C80 Series Alarm Parameter Manual 14 Multi CPU Errors A C80 198 IB 1501279 H ...
Page 216: ...199 IB 1501279 H Parameter ...
Page 217: ...M800 M80 E80 C80 Series Alarm Parameter Manual 200 IB 1501279 H ...
Page 218: ...15 201 IB 1501279 H User Parameters ...
Page 359: ...M800 M80 E80 C80 Series Alarm Parameter Manual 15 User Parameters 342 IB 1501279 H ...
Page 360: ...16 343 IB 1501279 H Machine Parameters ...
Page 748: ......