Parameters and firmware blocks
141
16.09
USER SET SEL
FW block: None
Enables the save and restoration of up to four custom sets of parameter settings.
The set that was in use before powering down the drive is in use after the next power-up.
Note:
Any parameter changes made after loading a user set are not automatically stored into the
loaded set – they must be saved using this parameter.
(1)
No request
Load or save operation complete; normal operation.
(2)
Load set 1
Load user parameter set 1.
(3)
Load set 2
Load user parameter set 2.
(4)
Load set 3
Load user parameter set 3.
(5)
Load set 4
Load user parameter set 4.
(6)
Save set 1
Save user parameter set 1.
(7)
Save set 2
Save user parameter set 2.
(8)
Save set 3
Save user parameter set 3.
(9)
Save set 4
Save user parameter set 4.
(10)
IO mode
Load user parameter set using parameters
16.10
USER SET LOG
FW block: None
Shows the status of the user parameter sets (see parameter
). Read-only.
N/A
No user sets have been saved.
(1)
Loading
A user set is being loaded.
(2)
Saving
A user set is being saved.
(4)
Faulted
Invalid or empty parameter set.
(8)
Set1 IO act
User parameter set 1 has been selected by parameters
and
.
(16)
Set2 IO act
User parameter set 2 has been selected by parameters
and
.
(32)
Set3 IO act
User parameter set 3 has been selected by parameters
and
.
(64)
Set4 IO act
User parameter set 4 has been selected by parameters
and
.
(128)
Set1 par act
User parameter set 1 has been loaded using parameter
(256)
Set2 par act
User parameter set 2 has been loaded using parameter
(512)
Set3 par act
User parameter set 3 has been loaded using parameter
(1024)
Set4 par act
User parameter set 4 has been loaded using parameter
Summary of Contents for ACSM1 Series
Page 1: ...ABB motion control drives Firmware manual ACSM1 motion control program ...
Page 4: ......
Page 34: ...Drive programming using PC tools 34 ...
Page 86: ...Drive control and features 86 ...
Page 265: ...Parameters and firmware blocks 265 1 100 us 100 µs 2 1 ms 1 ms 3 50 ms 50 ms ...
Page 302: ...Parameter data 302 ...
Page 422: ...Application program template 422 ...
Page 430: ...Appendix A Fieldbus control 430 ...
Page 500: ...Appendix D Application examples 500 ...
Page 508: ...Appendix E Control chain and drive logic diagrams 508 ...
Page 510: ...3AFE68848270 REV H EN 2015 06 26 Contact us www abb com drives www abb com drivespartners ...